This prefabricated modular data center is built around 18 IT cabinets on a 6000 x 3600 x 2000 mm footprint, with 5 kW of power per cabinet. Power is backed by a modular N+1 UPS built from 25kVA modules (4+1), so capacity can be added module by module as the hall fills up instead of over-building the electrical plant on day one.
Cooling is delivered by in-row precision air conditioning — four 31.1 kW units in a 3+1 redundant arrangement — mounted inside the cabinet row so cold air is released directly beside the heat load. Combined with cold / hot aisle containment, that keeps the two air streams separated and holds PUE down, while the modular frame stays ready for chilled-water or direct-to-chip liquid cooling once rack densities climb past 15 kW.
| Configuration | IT Cabinets | Power / Cab | UPS System | Cooling Capacity | Refrigeration Type | Dimensions (L*W*H) |
|---|---|---|---|---|---|---|
| Plan 1 › | 12 Cabinets | 5 kW | 90K Rack Modular (15kVA modules, 4+1) |
25.5kW x 4 (3+1 Redundancy) |
In-Row AC | 4200 x 3600 x 2000 mm |
| Plan 2 › | 12 Cabinets | 5 kW | 120K Tower Modular (30kVA modules, 3+1) |
65.5kW x 2 (1+1 Redundant) |
In-Row AC | 4800 x 3600 x 2000 mm |
| Plan 3 › | 14 Cabinets | 5 kW | 120K Tower Modular (30kVA modules, 3+1) |
71.1kW x 1 (N Redundancy) |
Room-Level AC | 4800 x 3600 x 2000 mm |
| Plan 4 › | 14 Cabinets | 5 kW | 120K Tower Modular (30kVA modules, 3+1) |
Custom Capacity (Tailored) |
FAN WALL | 4800 x 3600 x 2000 mm |
| Plan 5 › | 18 Cabinets | 5 kW | Modular N+1 (25kVA modules, 4+1) |
31.1kW x 4 (3+1 Redundancy) |
In-Row AC | 6000 x 3600 x 2000 mm |
| Plan 6 › | 24 Cabinets | 5 kW | Modular N+1 (25kVA modules, 5+1) |
40.9kW x 4 (3+1 Redundancy) |
In-Row AC | 8400 x 3600 x 2000 mm |
| Custom › | ≤ 48 Cabinets | ≤ 15 kW | Max 500kVA (2N/N+1 Redundancy) |
Flexible Capacity (Row or Room) |
Air / Water / Chilled | Length ≤ 15000 mm |
Space Flexibility: Our modular platform is built for adjustability. We tailor aisle configurations (this plan ships with 18 cabinets) to accommodate odd-shaped rooms, lowered ceilings, or structural pillars, maximizing usable floor area within this 6000 x 3600 x 2000 mm footprint.
Efficient Air Management: The fully enclosed aisle containment solution physically separates cold and hot air pathways, eliminating mixing and enhancing cooling performance for dense IT equipment.
Grow-on-Demand: Begin with the required capacity and scale effortlessly. Our modular design enables you to seamlessly integrate additional cooling units and racks as operational needs increase.
Ready for Next-Gen Workloads: The 18 cabinets ship pre-configured for in-row precision air conditioning, with the modular frame ready to accept chilled-water or direct-to-chip liquid cooling circuits for densities exceeding 15kW per rack.
Tailored to diverse deployment scenarios—including small enterprise IT rooms, retrofitted traditional data centers and outdoor edge nodes—our modular data center solutions balance performance, cost and energy efficiency.
3-15 kW per Cabinet
All-in-one integrated cabinet design, plug-and-play deployment (1-3 days), remote intelligent monitoring. Ideal for edge endpoints like retail stores, ATMs and small enterprise IT rooms.
8-30 kW per Cabinet
Column-level prefabricated design, flexible expansion by rows, fits existing server rooms without major reconstruction. PUE 1.2-1.4, perfect for medium-density enterprise IT deployments.
15-40 kW per Cabinet
Airtight cold/hot aisle enclosure, 90%+ cold air utilization, PUE reduced to 1.2-1.3. Cost-effective upgrade for traditional open data centers to support high-density servers.
10-500 kW (20ft/40ft)
Prefabricated all-in-one container (20ft/40ft), dustproof/anti-vibration, deployable outdoors. Liquid cooling optional for AI high-density computing (PUE ≤1.1), ideal for edge & temporary computing needs.
Empowering next-generation infrastructure with superior thermal management for high-wattage computing demands.