| Brand Name: | Soeteck |
| Model Number: | DC0300H |
| MOQ: | 1 Set |
| Price: | Negotiable |
| Delivery Time: | 30-45 working days |
| Payment Terms: | D/A |
The Soeteck DC0300H Outdoor Enclosure Air Conditioner removes 300 W of heat from a telecom or electrical cabinet using a genuine 48 VDC compressor and DC fans, so it can be fed straight from a DC bus or a renewable/hybrid site supply. A 105 W power draw and a 221 x 136 x 386 mm mono-block package make it a door-mounted unit rather than another box beside the cabinet.
Because the cooling loop is closed, cabinet air is recirculated and filtered instead of drawn from outside, and the unit is rated IP55 for dust and low-pressure water jets. The built-in controller reports over RS485 and dry contacts, soft-start keeps inrush off the site supply, and the flange around the front face lets the unit be cut into a cabinet door and fixed from outside — an operating range of -40 °C to 55 °C covers both hot and cold deployments.
| Model No. | Cooling Capacity | Operating Temperature |
Dimensions (W×D×H) | Weight | Rated Power |
|---|---|---|---|---|---|
| DC0300H › | 300W | -40°C ~ 55°C | 221×136×386mm | 8.5kg | 105W |
| DC5001H › | 600W | -40°C ~ 55°C | 320×170×550mm | 16kg | 180W |
| DC1000H › | 1000W | -40°C ~ 55°C | 446×200×746mm | 25kg | 320W |
| DC1500H › | 1500W | -40°C ~ 55°C | 446×200×746mm | 29kg | 500W |
| DC2000H › | 2000W | -40°C ~ 55°C | 446×250×746mm | 34kg | 665W |
| DC3000H › | 3000W | -40°C ~ 55°C | 446×300×746mm | 52kg | 920W |
| DC4000H › | 4000W | -40°C ~ 55°C | 545×300×1330mm | 71kg | 1200W |
The DC0300H cools a cabinet with 300 W of capacity from a genuine 48 VDC compressor and DC fans, so it runs directly from a telecom DC bus or a renewable/hybrid supply without an inverter in front of it. Rated power is 105 W, soft-start keeps the inrush current from tripping the site supply, and an aluminium micro-channel condenser does the heat rejection in a package only 221 x 136 x 386 mm.
The enclosure is powder-coated sheet metal, and the unit is rated IP55 against dust and low-pressure water jets from any direction. Because the cooling loop is closed, the air inside the cabinet is recirculated rather than exchanged with outside air, which is what keeps dust and moisture away from the electronics at a roadside or rooftop site.
The built-in controller shows operating state on the front display and reports over RS485 or a dry-contact alarm pair, so an unattended site can raise a fault to the network operations centre instead of waiting for a site visit. Self-recovery and the usual protection functions restart the unit after a supply disturbance, which matters where nobody is on site to press a button.
One mono-block casting carries the compressor, condenser, fan and controller, and the flange around the front face lets the unit be cut into a cabinet door or wall and fixed from outside. Installation is a cut-out, four fixings and a DC feed — no refrigerant work on site, which is the point of a sealed 8.5 kg package for a remote enclosure.
Focus on the core cooling demands of high-density data center deployments, where our full range of premium products leverages advanced technological advantages to reliably safeguard continuous, efficient, and stable operation.
7.5-300 kW
Designed for medium to large data centers, these units provide precise temperature and humidity regulation for the entire room. They utilize raised-floor or overhead delivery to ensure consistent airflow distribution and equipment stability.
5.6-90.1 kW
Positioned directly between server racks, this solution brings cooling closer to the heat source. It minimizes airflow paths to maximize efficiency, making it the ideal choice for managing hot spots and high-density computing clusters.
3.5-12.5 kW
An all-in-one solution integrated directly inside the server cabinet. This closed-loop system handles ultra-high thermal loads with maximum energy efficiency, isolating sensitive equipment from the outside room environment and noise.
1.0-4.0 kW
Compact and durable cooling designed for outdoor telecom cabinets, battery compartments, and industrial control panels. These units ensure reliable operation in harsh environments by strictly controlling internal temperatures and blocking contaminants.
Empowering next-generation infrastructure with superior thermal management for high-wattage computing demands.